46-6 - DIN
Differential pressure regulators with flow limitation
USAGE
- Differential pressure and flow control
MEDIUM
Water and other liquids
Gases
VERSION
DIN
MEDIUM TEMPERATURE
2
to 150 °C /
35.6
to
302 °F
VALVE SIZE
DN 15
to
DN 50
PRESSURE RATING
PN 16
to
PN 25
FUNCTION
- Differential pressure limiter
- Flow limiter
APPLICATION
- Valve closes when the differential pressure rises
INSTALLATION
- Return flow pipe
FLOW RATE SET POINT
0.01 to 10.7 m³/h / 0.04 to 47.1 US gal/min
FLOW RATE DP ACROSS RESTRICTION
0.1 bar / 1.45 psi
DIFFERENTIAL PRESSURE SET POINT
0.2 to 2 bar / 2.9 to 29.01 psi
Special features
- Differential pressure regulators with flow limitation
- Consisting of valve with adjustable restriction and actuator with operating diaphragm
- Single-seated valve with balanced plug
- Particularly suitable for district heating systems according to DIN 4747-1
- Internal overload protection in the actuator
Accessories
- - - -
Options
- - - -
Information
T 3130
Type 46-5 and Type 46-6 Differential Pressure Regulators with Flow Limitation
[EN][DE]T 3095
Accessories · Differential pressure and flow regulators
[EN][DE]T 3120
Information Sheet:
Series 45, 46, 47 and 48 Self-operated Differential Pressure and Flow Regulators as well as Combined Reguators
[EN][DE]
Support
DXF file from data sheet
- T 3130 [ZIP]
Certificates
Only up-to-date documents are shown in the product selector. Check the documentation site for a list of all documents available.
Pin items on your list and contact us if you have any product-related questions.
Back to product selector